Description
General
The DC-9102E is a photoelectric (optical) detector suitable for use in hotels, restaurants, office buildings, schools, banks, warehouses, libraries, computer rooms, switch rooms, etc.
Application
The detector supports installation on the GST DB-01 conventional detector base for standard applications, or the GST DB-01D diode base when head-out functionality to BS5839 standard is required. Detection sensitivities are programmable using the GST P-9910B device programmer.
In details
- Supports drift compensation to enable good environmental adaptability
- Self-diagnostic
- Local test activation with reed switch
- Chamber contamination checking
- All round LED visibility (360° viewing angle) avoids time spent on specific detector orientation
- Configurable polling LED support
- Remote indicator output
- Removable sensing chamber for for easy maintenance
- 2 Programmable smoke sensitivity levels
datasheet :dc-9102e-1-en-za
Technical Specifications
General | |
---|---|
Status indication | Red LED |
User interface | Via LED – polling, fault, contamination and alarm |
Compatibility | GST100A Series conventional CIEs as well as GST I-9319 Zone Monitor |
Reset voltage | <1 VDC |
Reset time | >2 s |
Alarm levels | 2 |
Connectivity | Zone connection – 2-core (polarity sensitive), RI connection – 2-core (polarity sensitive) |
Electrical | |
---|---|
Operating voltage | 16 VDC to 28 VDC (24 VDC typical) |
Current consumption | <60 μA (Quiescent) ≤55 mA (Alarm) |
Cable specification | >1.0 mm² |
No. of cable cores | 2 |
Terminals | 4 |
Detection | |
---|---|
Detection principle | Optical |
Sensitivity | Programmable |
Zone length | Panel dependent |
Output | |
---|---|
Remote alarm output | 1 |
Physical | |
---|---|
Physical dimensions | 54.5 mm (including base) x 100 mm Ø |
Net weight | ±110 g |
Colour | White |
Mounting type | Ceiling mount |
Material (body) | ABS |
Environmental | |
---|---|
Vandal proof | No |
Operating temperature | -10 to +50°C |
Relative humidity | 0 to 95% noncondensing |
Environment | Indoor |
IP rating | IP2x |
Environment temperature | -10 to +50°C (Class A1/A2) |
-10 to +65°C (Class B) |
Regulatory | |
---|---|
Compliancy | CE, WEEE |
Certification | EN54-7 |
Standards | LPCB |